The MICRO PANELS from the product ranges XV100, XV200, XV400, XVS400, XVH300 and XV700 have a registered amount of license points. License points are needed to run specific functions on the unit:
- Runtime for the visualization (GALILEO or EPAM)
- Communication (e.g. Ethernet, CANopen, Siemens MPI)
- Tools (e.g. CE-Telediag, S7 PG router)
- MXpro-Runtime for PLC functionality (not possible with a XVH300 )
To access the needed function of the unit you must activate a specific amount of license points. Standard units posses 140 license points on delivery and allow e.g.:
- Visualization functionality GALILEO-Runtime (100 license points)
- Communication to an external PLC via Siemens MPI (40 license points)
If the amount of registered license point on the unit is not enough to access all needed functions then the license points total has to be increased. For this you need one or more license product papers. License product papers can be order from you Micro Innovation product dealer.
Conversion of a License Product Paper
- Order the needed license product paper from your Micro Innovation supplier.
- Supply the following data:
- License product paper certificate
- Serial-no. of the unit
- Your email address
- Go to the Micro Innovation homepage (http://www.microinnovation.com) to the menu item Validate license product papers and click >>> Start Licensing <<<.
Follow the dialog that appears in the window.
- Enter the license code with help of the tool „License Administrator“ in the control panel of the unit.
Determination of the necessary needed license points
-
License points certificate for PLC function:
For the activation of the PLC function (MXpro) a special license product paper is needed („PLC license product paper“). This includes a license sticker fitting to the unit that has to be applied to the unit because of legal licensing issues.
-
License points certificates for visualization, communication and tools:
For the visualization, used communication and tools sum the total needed points for all functions. Communication to multiple units with the same protocol has to be paid for once. Subtract from this amount the already on the unit installed license points (e.g. 140). The difference is number of license points that have to be added over license product papers for communication and tools.
Example for determination of the needed license product papers
Number of required license points for XV100 / XV200 / XV400 / XVS400 / XVH300 and XV700 depending on the required functionality:
0-120 (number value) : communication available, needed license amount
- : communication currently not available
Tools:
| Runtime/Tools |
Onboard interface |
License points |
| GALILEO-Runtime |
- |
100 |
| EPAM-Runtime |
- |
100 |
| MXpro-Runtime |
- |
100 |
| CE Telediag |
RS232 |
40 |
| S7 PG Router |
Ethernet and Profibus |
80 |
| CAN Monitor |
CAN |
- |
Communications by On-Board interfaces:
| Manufacturer |
Control |
Protocol |
Onboard interface |
Lic.pts. MXpro |
Lic.pts. GALILEO |
Lic.pts. EPAM |
| Micro Innovation |
MXpro |
|
lokal |
- |
0 |
0 |
| Micro Innovation |
MXpro |
|
Ethernet |
0 |
40 |
0 |
| Micro Innovation |
DXS |
|
Ethernet |
- |
80 |
- |
|
|
CAN Open Master |
CAN |
0 |
- |
- |
|
|
CAN Open PDO |
CAN |
0 |
40 |
- |
|
|
CAN Open SDO |
CAN |
0 |
40 |
- |
|
|
DP-Master (1.5 MBaud) |
Profibus |
40 |
- |
- |
|
|
Modbus RTU |
RS232 |
- |
40 |
- |
|
|
Modbus TCP |
Ethernet |
- |
80 |
- |
|
CoDeSys |
|
Ethernet |
0 |
40 |
0 |
| A. Bradley |
Logix |
DF1 |
RS232 |
- |
120 |
- |
| A.Bradley |
Logix |
EtherNet/IP |
Ethernet |
- |
120 |
- |
| Beckhoff |
TwinCAT |
ADS |
Ethernet |
- |
80 |
- |
| Delta Tau |
PMAC |
|
RS232 |
- |
40 |
- |
| HIMA |
HIMatrix |
Modbus TCP |
Ethernet |
- |
80 |
- |
| Moeller |
easy 800 / easy MFD |
|
RS232 |
- |
40 |
- |
| Moeller |
PS4 |
|
RS232 |
- |
40 |
- |
| Moeller |
XControl |
|
CAN |
- |
40 |
- |
| Moeller |
XControl |
|
Ethernet |
- |
40 |
- |
| Moeller (on XVH342-57SKS) |
|
Suconet K |
Suconet K |
- |
0 |
- |
| Siemens |
S7 |
Industrial Ethernet |
Ethernet |
- |
80 |
- |
| Siemens |
S7 |
MPI |
Profibus |
- |
40 |
- |
| Siemens |
S7 |
Profibus DP (1.5 MBaud) |
Profibus |
- |
40 |
- |
| Siemens |
S7-200 |
PPI |
Profibus |
- |
40 |
- |
Contact your Micro Innovation representative for any enquiries about other protocols.